EasyManua.ls Logo

alphatronics AlphaVision ML - Page 11

alphatronics AlphaVision ML
124 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installer manual AlphaVision ML Rev. 3.60 01-01-2015 11
Test institute: the testing and approval in accordance with above mentioned standards were performed by
Telefication BV, Zevenaar, The Netherlands (see www.telefication.com).
Casing control panel: Synthetic casing; 238 x 188 x 92 mm (H x W x D), including battery pack. Weight:
1156gr, including batterypack.
Metal cabinet; 400 mm x 255 mm x 120 mm (H x W x D), excluding lead acid battery. Weight: 5300gr,
including batterypack.
Casing I/O module: Metal cabinet; 400 mm x 255 mm x 120 mm (H x W x D), excluding lead acid battery.
Weight: 5300gr, including batterypack.
Keypad: ML/LCD PROX, synthetic casing; 165mm x 125mm x 26mm (H x B x D). Weight: 271gr.
PSTN plug-on board: No casing, is plugged directly onto the AlphaVision ML mainboard. Print dimensions:
80mm x 50mm x 11mm (H x B x D). Weight: 45gr.
GSM plug-on board: No casing, is plugged directly onto the AlphaVision ML mainboard. Print dimensions:
110mm x 42mm x 19mm (H x B x D). Weight: 32gr.
Working temperature: 0° C to +40° C
Storage temperature: -20° C to +60° C
Humidity: 85% relative humidity
Power: Type A (power supply with back-up, PRIMARY (nominal input voltage / frequency), 230 VAC / 50 Hz
(+10% / -15%). At full load primarily up to 0.5A is consumed (@ 230VAC). SECONDARY 16VDC/1.9A (± 3%),
maximum ripple / noise is 250mV. The power supply complies with EN60950.
Battery: The maximum battery capacity, which is used in combination with the Alpha Vision ML can be
2700mAh (rechargeable battery type Sanyo 12V 2.7 Ah NiMH).
Low Battery: Low battery voltage is detected when the voltage of the battery drops below 10.7VDC (± 10%)
(SD low voltage).
Power output : For all terminals where an output voltage is available (the +12 V terminals) the following
applies: maximum voltage is 15.5 VDC, nominal voltage is 12VDC and minimum voltage is 9VDC.
Max. output current: Taking into account the power consumption of the Alpha Vision ML pcb board and the
maximum charging current of the battery, the maximum continuous power for other components
connected may be 65mA. If more power is desired or necessary, an I/O module with its own power supply
must be installed.
Current drain: The mainboard consumes 133mA in idle state with an LCD panel (backlight not illuminated)
connected 15mA. For extra details, see the chapter on power consumption and cabling .
The main board of the AlphaVision ML is equipped with an integrated IP dialer, 12 hard-wired inputs (zones
1 to 12) and 4 outputs. The four outputs are composed of two potential free relay contacts and two open
collector outputs. The AlphaVision ML is always delivered with a LCD or LCD/PROXIMTY keypad.

Table of Contents