5-43
Chapter 5. Functions
Operation starts with the down-ramp in step 1
SP (for LSP1)
Slope of step 1 ramp
Step 1READY
Step 2 Step 3
STEP loop
The operation when a step operation ends (loop back, etc.) can be specified.
Item (bank) Display Description Initial value User level
STEP loop
(setup bank)
C 35
0: Operation stops (no loop-back)
1: Loops back
2: Continues SOAK with the final step’s SP
(no loop-back)
0 Advanced
• 0: This device enters READY mode when the SOAK of the final step ends.
• 1: When the SOAK of the final step ends, step operation is repeated starting with
the RAMP in step 1. In this RAMP, regardless of the setting of
C34
(STEP PV
start), the SP of the final step ramps up to the SP for LSP 1. There is no limit on
the number of loops. Therefore, looping will continue until the operation mode is
switched to READY.
• 2: When the SOAK of the final step ends, SOAK continues at the SP of the final
step until the operation mode is switched to READY.