5-69
Chapter 5. Functions
MV1/MV2 processing
The time proportional cycle and time proportional cycle mode for MV1 and MV2
can be specified.
Item (bank) Display Description Initial value User level
Time proportional cycle 1
(for MV1)
(parameter bank)
CY
5 to 120 s
(when the output includes the relay
output)
1 to 120 s
(when the output does not include the
relay output)
10 or 2 s Simple,
standard,
advanced
Time proportional cycle 2
(for MV2)
(parameter bank)
CY2
10 or 2 s
Time proportional cycle mode
(parameter bank)
TP.TY
0: Priority on controllability
1: Priority on actuator service life (only
one ON/OFF operation in a time
proportional cycle)
0 or 1 Advanced
Time proportional minimum
ON/OFF time 1 (for MV1)
(parameter bank)
TPO
0 to 250 ms 0 Advanced
Time proportional minimum
ON/OFF time 2 (for MV2)
(parameter bank)
TPO2
0 to 250 ms 0 Advanced
MV1: ON/OFF control output, time proportional output, heating time
proportional output of heating/cooling control
MV2: Cooling time proportional output of heating/cooling control
In the DO assignment bank, if MV1 is connected to any of relay control output,
voltage pulse control output, or event output, time proportional cycle 1 (Cy) is
displayed and the setting can be changed.
If heating/cooling control is used and, in the DO assignment bank, if MV2 is
connected to any of relay control output, voltage pulse control output, or event
output, time proportional cycle 2 (Cy2) is displayed and the setting can be
changed.
The initial value of time proportional cycle 1 (Cy) is 2 if the control output 1 is a
voltage pulse output, and 10 otherwise.
The initial value of time proportional cycle 2 (Cy2) is 2 if the control output 2 is a
voltage pulse output, and 10 otherwise.
The time proportional cycle mode (tP.ty) setting is valid for both MV1 and MV2
time proportional outputs.
If MV1 is connected to the relay control output or event output in the DO
assignment bank and if time proportional cycle 1 (Cy) is set to shorter than 5s,
5s applies.
If MV2 is connected to the relay control output or event output in the DO
assignment bank and if time proportional cycle 2 (Cy2) is set to shorter than 5s,
5s applies.