5-70
Chapter 5. Functions
The minimum ON/OFF time is the minimum time to maintain the output status
after switching the output ON/OFF. Until this time elapses, the output status is
maintained even if the time to switch ON/OFF comes.
If time proportional minimum ON/OFF time 1 = 0: If MV1 is connected to
the relay control output or event output in the DO assignment bank, or if time
proportional cycle 1 is 10 s or longer, 250 ms applies. Otherwise, 1 ms applies.
If time proportional minimum ON/OFF time 1 = 1–250: If MV1 is connected to
the relay control output or event output in the DO assignment bank, and if the
setting is 1–49, 50 ms applies. If the setting is 50–250, the set value applies.
If time proportional minimum ON/OFF time 2 = 0: If MV2 is connected to
the relay control output or event output in the DO assignment bank, or if time
proportional cycle 2 is 10 s or longer, 250 ms applies. Otherwise, 1 ms applies.
If time proportional minimum ON/OFF time 2 = 1–250: If MV2 is connected to
the relay control output or event output in the DO assignment bank, and if the
setting is 1–49, 50 ms applies. If the setting is 50–250, the set value applies.
Handling Precautions
The shorter the time proportional cycle, the better the controllability.
However, when specifying the settings, please take the electrical service
life of the relay into consideration.