Chapter 9. PLC Link Communication Function
Precautions for the PLC link communication function
When the PLC link communication function is used, RS-485 communication
with the host device cannot be used.
Do not connect anything other than the C1M and one PLC unit to the RS-485
communication line.
Set the C1M addresses from 1 to the maximum number of connected C1M units.
The maximum number of connected C1M units can be selected from 8 (default),
16, 24, and 31.
The PLC’s device ID and the C1M’s station address must be different.
Do not use 255 or 254 as the device ID of the PLC.
New settings will apply after the power of the device is turned off and back on. If
you have changed the settings, turn the power off and back on.
Use the required number of consecutive registers on the PLC.
Different protocols cannot be used at the same time.