5-35
Chapter 5. Functions
SP ramp unit
The time unit of the SP ramp can be specified.
Item (bank) Display Description Initial value User level
SP ramp unit
(setup bank)
C 32
0: 0.1 U/s
1: 0.1 U/min
2: 0.1 U/h
1 Advanced
• 0.1 U means that the setting displayed has one more decimal place than the
number of decimal places set by “PV decimal point position.”
Examples
For a thermocouple input with a range of −200 to + 200 °C: 0.1 U = 0.1 °C
For a DC voltage input with a range of 0.0 to 100.0: 0.1 U = 0.01
SP up ramp / down ramp (p.5-36) (for the relationship between PV input
ranges with a decimal point and the setting for “PV decimal point position”)
Handling Precautions
• For a DC voltage input or DC current input with the 3-decimal place
setting, 0.1 U = 0.0001.
However, regarding the SP up ramp and SP down ramp settings, all four
values displayed on this device indicate values after the decimal point,
because this device can display only four digits.