5-55
Chapter 5. Functions
5 - 8 Internal Events
The result of internal event processing can be output as control outputs or event outputs via the digital output (DO)
processing circuit.
Chapter 2. Outline of Functions (p.2-1) (for details)
The following is a functional block diagram for internal events.
Operation type
(Event configuration bank, operation type
E1.C1 to E5.C1)
Direct/reverse, standby
(event configuration bank, direct/reverse, standby
E1.C2 to E5.C2)
Main setting, sub-setting, hysteresis, special OFF
(Event bank,
E1 to E5, E1.Sb to E.Sb, E1.Hy to E5.Hy,
Event configuration bank,
E1.C3 to E5.C3)
Alarm OR/AND
(Event configuration bank,
E1.C3 to E5.C3)
ON delay time, OFF delay time, delay time unit
(Event bank,
E1.On to E5.On, E1.OF to E5.OF
Event configuration bank, E1.C3 to E5.C3)
Event state in READY
(Event configuration bank,
E1.C2 to E5.C2)
Internal event status
Handling Precautions
There are 5 internal events numbered 1 to 5. The number of event outputs
(0–3) can be selected by specifying the appropriate model No. When the
product is shipped, the operation results of internal events 1 to 3 are set to
be output from event output terminals 1 to 3. To use the operation results of
internal events 4 to 5, specify the settings in the DO assignment bank.