6-37
Chapter 6. Displayed Items and Settings
Display Item Description Initial
value
User
level
Notes
Ev3.1
Event output 3
operation type
Same as control output 1 operation type
0: Default output
1: MV1
2: MV2
3-6: Functions 1-4
0 0 Displayed if a model with event
output 3 is used.
For event output 3, the default
output is internal event 3.
Ev3.2
Event output 3
output assignment A
Same as control output 1 output
assignment A to D
0 to 49
4 2 Displayed if event output 3 is
selected by the model No. and
event output 3 operation type
is set to one of functions 1–4
(Ev3.1 > 2).
Ev3.3
Event output 3
output assignment B
0 2
Ev3.4
Event output 3
output assignment C
0 2
Ev3.5
Event output 3
output assignment D
0 2
Ev3.6
Event output 3
polarity A to D
“1st digit” (2nd, etc.) means the first digit
(etc.) from the right.
2
1st digit: Polarity A 0: Direct
1: Reverse
0
2nd digit: Polarity B 0
3rd digit: Polarity C 0
4th digit: Polarity D 0
Ev3.7
Event output 3
polarity
0: Direct
1: Reverse
0 2
Ev3.8
Event output 3 latch 0: Do not latch
1: Latch when ON
2: Latch when OFF (except for
initialization at power-on)
0 2