10-12
Chapter 10. List of Communication Data
Bank Item RAM address EEPROM address RAM EEPROM Decimal
point
Notes
Decimal Hexa-
decimal
Decimal Hexa-
decimal
Read Write Read Write
Operation
settings
PV 9101 238D 25485 638D
P Same as RAM address
14356 (decimal).
SP (target value) 9102 238E 25486 638E P
*2
LSP group selection 9103 238F 25487 638F
− Same as RAM address
14592 (decimal).
Writable when not as-
signed to a DI.*
3
(Reserved for future use.) 9104 2390 25488 6390
−
MV (Manipulated Variable) 9105 2391 25489 6391
1 Same as RAM address
14594 (decimal).
Writable in manual mode
Heat MV (Manipulated Variable) 9106 2392 25490 6392
1 Same as RAM address
14420 (decimal).
Cool MV (Manipulated Variable) 9107 2393 25491 6393
1 Same as RAM address
14421 (decimal).
(Reserved for future use.) 9108 2394 25492 6394
1 Same as RAM address
14417 (decimal).
AT progress 9109 2395 25493 6395
−
CT1 current 9110 2396 25494 6396
1 Same as RAM address
14418 (decimal).
CT2 current 9111 2397 25495 6397
1 Same as RAM address
14419 (decimal).
Timer remaining time 1 9112 2398 25496 6398
S
Timer remaining time 2 9113 2399 25497 6399
S
Timer remaining time 3 9114 239A 25498 639A
S
Timer remaining time 4 9115 239B 25499 639B
S
Timer remaining time 5 9116 239C 25500 639C
S
(Reserved for future use.) 9117 239D 25501 639D
S
(Reserved for future use.) 9118 239E 25502 639E
S
(Reserved for future use.) 9119 239F 25503 639F
S
Step No.
9120 23A0 25504 63A0
S
Step remaining time
9121 23A1 25505 63A1
S
Step remaining time (second)
9122 23A2 25506 63A2
S
LSP in use 9123 23A3 25507 63A3 P Same as RAM address
14593 (decimal).*
2
PV (before ratio,bias,filter) 9124 23A4 25508 63A4
P
(Reserved for future use.) 9125 23A5 25509 63A5
P
*2. If a value is read immediately after writing it to an SP or LSP that is in use, the value may not have changed yet.
Values are updated after the control cycle time ends.
*3. If an SP or LSP that is in use is read immediately after writing the value to the LSP group selection, the value may not have changed yet.
Values are updated after the control cycle time ends.