10-14
Chapter 10. List of Communication Data
Bank Item RAM address EEPROM address RAM EEPROM Decimal
point
Notes
Decimal Hexa-
decimal
Decimal Hexa-
decimal
Read Write Read Write
Status Internal event / internal contact func-
tion status
9203 23F3 25587 63F3
Bits 0–4:
Internal events 1–5
Bits 5–7: Undefined
Bits 8-10:
Internal contacts 1-3
Bits 11–15: Undefined
Control status 9204 23F4 25588 63F4
Bit 0: MANUAL mode
0: AUTO
1: MANUAL
Bit 1: READY mode
0: RUN mode
1: READY mode
Bit 2: Undefined
Bit 3: AT is in progress
Bits 4–5: Undefined
Bit 6: During SP ramp
Bit 7:
SP ramp-up is in progress
Bit 8:
SP ramp-down is in
progress
Bits 9–12: Undefined
Bit 13:
Heating PID is in use*
Bit 14:
Cooling PID is in use*
Bit 15: Undefined
DO state 9205 23F5 25589 63F5
Same as RAM address
14337 (decimal).
Bit 0: Control output 1
Bit 1: Control output 2
Bit 2: Event output 1
Bit 3: Event output 2
Bit 4: Event output 3
Bits 5–15: Undefined
DI state 9206 23F6 25590 63F6
Same as RAM address
14338 (decimal).
Bit 0: DI1
Bit 1: DI2
Bit 3: Undefined
User-defined bit 9207 23F7 25591 63F7 Bit 0:User-defined bit 1
Bit 1:User-defined bit 2
Bit 2:User-defined bit 3
Bit 3:User-defined bit 4
User-defined bit 1 9208 23F8 25592 63F8
User-defined bit 2 9209 23F9 25593 63F9
User-defined bit 3 9210 23FA 25594 63FA
User-defined bit 4 9211 23FB 25595 63FB
* Valid only if C26 (heat/cool control) is set to 1 (use (individual PID))