9 Communication
9.2 EtherNet / IP
232 Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
P2-02 f-Fix3 202 R/W 0x04 0x18 0x19 1 U16 0.0 - P1-01 0 – 3000 ≙
0–50 Hz
40.0 Hz
P2-03
f-Fix4 203 R/W 0x04 0x18 0x19 1 U16 0.0 - P1-01 0 – 3000 ≙
0–50 Hz
50.0 Hz
P2-04
f-Fix5 204 R/W 0x04 0x18 0x19 1 U16 0.0 - P1-01 0 – 3000 ≙
0–50 Hz
10.0 Hz
P2-05
f-Fix6 205 R/W 0x04 0x18 0x19 1 U16 0.0 - P1-01 0 – 3000 ≙
0-50Hz
15.0 Hz
P2-06
f-Fix7 206 R/W 0x04 0x18 0x19 1 U16 0.0 - P1-01 0 – 3000 ≙
0–50 Hz
20.0 Hz
P2-07
f-Fix8 207 R/W 0x04 0x18 0x19 1 U16 0.0 - P1-01 0 – 3000 ≙
0–50 Hz
25.0 Hz
P2-08
t-SRamp1 208 R/W 0x04 0x18 0x19 1 U16 0.0 - 10.0 s 100 ≙ 10,0 s 0,0 s
P2-09
Overvoltage control 209 R/W 0x04 0x18 0x19 1 U16 0 - 1 – 1
P2-10
REV enable 210 R/W 0x04 0x18 0x19 1 U16 0 - 1 – 0
P2-11
t-acc2 211 R/W 0x04 0x18 0x19 1 U16 0.0 - 3000.0 s 300 ≙ 30,0 s 5,0 s
P2-12
n-accMulti1 212 R/W 0x04 0x18 0x19 1 U16 0.0 - P1-01 – 0.0 Hz
P2-13
t-dec2 213 R/W 0x04 0x18 0x19 1 U16 0.0 - 3000.0 s 300 ≙ 30,0 s 5,0 s
P2-14
n-decMulti1 214 R/W 0x04 0x18 0x19 1 U16 0.0 - P1-01 0 – 3000 ≙
0–50 Hz
0.0 Hz
P2-15
f-Skip1 215 R/W 0x04 0x18 0x19 1 U16 0.0 - P1-01 0 – 3000 ≙
0–50 Hz
0.0 Hz
P2-16
f-SkipBand1 216 R/W 0x04 0x18 0x19 1 U16 0.0 - P1-01 0 – 3000 ≙
0–50 Hz
0.0 Hz
P2-17
f-Skip2 217 R/W 0x04 0x18 0x19 1 U16 0.0 - P1-01 0 – 3000 ≙
0–50 Hz
0.0 Hz
P2-18
f-SkipBand2 218 R/W 0x04 0x18 0x19 1 U16 0.0 - P1-01 0 – 3000 ≙
0–50 Hz
0.0 Hz
P2-19
V/f-Characteristic 219 R/W 0x04 0x18 0x19 1 U16 0 - 2 – 0
P2-20
f-MidV/f 220 R/W 0x04 0x18 0x19 1 U16 0.0 ±100 % – 0.00 %
P2-21
V-MidV/f 221 R/W 0x04 0x18 0x19 1 U16 0.0 ±100 % – 0.00 %
P2-22
Switching frequency 222 R/W 0x04 0x18 0x19 1 U16 0 - 5 0 1
P2-23
Auto Thermal Management 223 R/W 0x04 0x18 0x19 1 U16 0 - 1 – 0
P2-24
Start mode 224 R/W 0x04 0x18 0x19 1 U16 0 - 10 – 0
P2-25
REAF start function 225 R/W 0x04 0x18 0x19 1 U16 0 - 2 – 0
P2-26
Auto Reset Delay 226 R/W 0x04 0x18 0x19 1 U16 0.1 - 60.0 s 300 ≙ 30,0 s 0,5 s
P2-27
Action@Thermistorfault Motor 227 R/W 0x04 0x18 0x19 1 U16 0 - 1 – 1
P2-28
Service interval Time 228 R/W 0x04 0x18 0x19 1 U16 0 - 60000 – 0 h
P2-29
Reset ServiceIndicator 229 R/W 0x04 0x18 0x19 1 U16 0 - 1 – 0
P2-30
Parameter set 230 R/W 0x04 0x18 0x19 1 U16 0 - 1 – 0
P2-31
Default selection 231 R/W 0x04 0x18 0x19 1 U16 0 - 1 – 0
P2-32
Access key level2 232 R/W 0x04 0x18 0x19 1 U16 0 - 65535 – 101
P2-33
Parameter lock 233 R/W 0x04 0x18 0x19 1 U16 0 - 1 – 0
P2-34
TCP Enable Service 234 R/W 0x04 0x18 0x19 1 U16 0 - 15 – 0
P2-36
Save parameter @24V-ext. 236 R/W 0x04 0x18 0x19 1 U16 0 - 1 – 0
Parameters
Designation
Instance
Access right
Object class
Service code
Read
Service code
Write
Length (word)
Data format
Value
range
Scaling
Default
setting