6 – 212 HEIDENHAIN Technical Manual TNC 426, TNC 430
6.12.11 Speed Controller (Only TNC 426 PB/M, TNC 430 PA/M)
A digital speed controller for the spindle is integrated in the TNC 426 PB/M and
TNC 430 PA/M:
7
77
7 With MP2501.x adjust the proportional factor, and with MP2511.x the
integral factor of the speed controller of the first spindle.
With Module 9164 you can read the actual speed value of the motor. (See "The
Control Loop” on page 6 – 109).
For the speed controller of the spindle, you can define the differential factor,
the low-pass filter, PT
2
second-order time-delay element, and the band-
rejection filter (See "Commissioning” on page 6 – 462).
7
77
7 In MP2521.0–1, enter the differential factor.
7
77
7 If required, enter the filter order in MP2561.
7
77
7 If required, in MP2531.0–1 enter the PT
2
second-order time delay element.
7
77
7 If required, enter in MP2541 and MP2551 the band-rejection filter damping
and the center frequency.
MP2501.0-1 Proportional factor of the spindle speed controller for wye
and delta connection
Input: 0 to 100 000 000.000 [As]
MP2511.0-1 Integral-action factor of the spindle speed controller for
wye and delta connection
Input: 0 to 100 000 000 [A]
MP2521.0-1 Differential factor of the spindle speed controller for wye
and delta connection
Input: 0 to 1.0000 [As
2
]
MP2531.0-1 PT
2
second-order time delay element of the speed
controller for the first spindle for wye and delta connection
Input: 0 to 1.0000 [s] 0 = 0.001 s
MP2541 Band-rejection filter damping
Input: 0.0 to 18.0 [dB]
MP2551 Band-rejection filter for center frequency
Input: 0.0 to 999.9 [Hz]
MP2561 Low-pass filter
Input: 0: No low-pass filter
1: 1st-order low-pass filter
2: 2nd-order low-pass filter