December 2001 Display and Operation 6 – 275
Display/delete
PLC soft key
7
77
7 Procedure for displaying/deleting a PLC soft key
Module 9201 Display/delete PLC soft key
If no PLCSOFTK.SYS file exists, or if the specified line does not exist, no soft
key is generated. In an existing PLC soft-key level, the soft key is displayed/
deleted at the specified position.
Can only be called from the sequential program.
Call:
PS B/W/D/K <Soft-key number (line no./delete)>
0: Line no.
–1: Delete soft key
PS B/W/D/K <Position no.>
0 to 31
PS B/W/D/K <Soft-key mode>
0: Soft key for displayed PLC window
1: Soft key in current operating mode
2: Append soft key to NC soft key
CM 9201
Error recognition:
Select/deselect
PLC soft keys and
PLC windows
Module 9202 Select/deselect PLC soft keys and PLC windows
With this Module 9202 you activate the display with PLC windows or the PLC
soft-key display. This module works like the screen management key.
Call:
PS B/W/D/K <Display mode>
0: PLC soft key/window deselected
1: Small PLC soft key/window deselected
2: Large PLC soft key/window deselected
3: Large PLC soft key/window selected while table editor is
active
CM 9202
Error recognition:
Marker Value Meaning
M4203 0 No error
1 Error code in W1022
W1022 1 Transfer parameter out of value range
2 Line nr. < –1
24 Module was called in a submit job
Marker Value Meaning
M4203 0 No error
1 Error code in W1022
W1022 1 Transfer parameter out of value range