Model IFP-2000/ECS Installation Manual 151430-L8
7-1
Section 7
IDP and SD SLC Device Installation
7.1 List of IDP SLC Devices
The following IDP SLC devices can be used with the control panel. See the device installation instructions
(packaged with the device) for more information.
Note: The control panel supports the use of either IDP SLC devices or SD SLC devices. You cannot install both
SLC device types on the control panel.
Caution!
To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while installing or
servicing.
Part Numbers Model Name/Description
Installation
Sheet PN
IDP-Photo Photoelectric smoke detector I56-3611-000
IDP-Photo-T Photoelectric smoke detector with thermal (135°F)
IDP-Acclimate Multi-criteria photoelectric smoke detector with thermal (135°F)
IDP-PhotoR Photoelectric replacement smoke detector with remote test capability in DNR I56-3569-000
IDP-Beam Reflected beam smoke detector without test feature I56-2735-00
IDP-Beam-T Reflected beam smoke detector with test feature
DNR/DNRW Duct smoke detector housing. Non-relay (photo sold separately) I56-3051-000
IDP-Heat Fixed temperature thermal detector (135°F) I56-3608-000
IDP-Heat-ROR Rate-of-rise thermal detector with 135° fixed temperature
IDP-Heat-HT Fixed high temperature thermal detector (190°F)
IDP-Pull-SA Addressable single action pull station I56-3606-000
IDP-Pull-DA Addressable dual action pull station I56-3605-000
IDP-ISO Fault isolator module I56-2729-000
ISO-6 Six Fault isolator module I56-4096-000
IDP-Monitor Monitor module I56-3603-000
IDP-Minimon Mini monitor module I56-2726-002
IDP-Monitor-2 Dual input monitor module I56-2730-000
IDP-Monitor-10 10 input monitor module I56-2731-000
IDP-Relay Relay module I56-2729-000
IDP-Relay-6 Six circuit relay module I56-2729-000
IDP-RelayMon-2 Multi module with 2 relay outputs & 2 monitor inputs I56-3734-000
IDP-Zone Zone interface module I56-3602-000
IDP-Zone-6 Six zone interface module I56-2733-000
IDP-Control Supervised control module I56-3600-000
IDP-Control-6 Six circuit supervised control module I56-2734-000
IDP-FIRE-CO CO Smoke Detector I56-3946-00
B200S/IV Intelligent sounder base. White or Ivory I56-3387-00
B200SR/IV Intelligent sounder base. White or Ivory I56-3392-00

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Farenhyt IFP-2000 and is the answer not in the manual?

Honeywell Farenhyt IFP-2000 Specifications

General IconGeneral
BrandHoneywell
ModelFarenhyt IFP-2000
CategoryConference System
LanguageEnglish

Related product manuals