Model IFP-2000/ECS Installation Manual 151430-L8
9-1
Section 9
Programming
This section of the manual describes how to manually program the control panel from the built-in annunciator.
Each subsection discusses these menu options in detail. All options described in this section can be performed
using Silent Knight Software Suite (SKSS-2).
9.1 UL 864 / UL 2572 Programming Requirements
9.2 Modules
This section lists the options available under the module option in the Panel Programming. The following
modules are available for the control panel: 5824 serial/parallel/IO printer interface module, RA-2000 remote
fire alarm annunciator, 5815XL SLC expander, RPS-1000 intelligent power module, 5496 intelligent power
Important!
Before any customized programming is done, JumpStart AutoProgramming should be run first. After
JumpStart is run, thoroughly test the system. The reason the system should be tested after JumpStart
AutoProgramming is because JumpStart AutoProgramming automatically programs the system, searching
for and configuring all SLC and SBUS devices it finds. JumpStart allows you to confirm the integrity of the
installation prior to performing any custom programming. After determining that the hardware is properly
installed, custom programming can be performed. Refer to Section 8.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES:
This product incorporates field programmable software. In order for the product to comply with the requirements in
the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, and Stand for Mass Notifications
Systems, UL 2572, certain programming features or options must be limited to specific values or not used at all as
indicated below.
Programming
Option
Menu Item
Permitted in
UL 864
(Y/N)
Permitted in
UL 2572 (Y/
N)
Possible
Settings
Settings
Permitted in UL
864
Settings
Permitted in
UL 2572
Time Options Low AC
Report Delay
Yes Yes 0–30 hours 1–3 1–3
Display Oldest
Event
Y (Enabled) Yes Yes Yes & No Yes Yes
N (Disabled) No No Yes & No No No
Initial Delay 0-28 Yes Yes 0-28 3-10 4-28
Inter Message Delay 4-32 Yes Yes 4-32 4-32 4-28
Alarm Verification Alarm
Verification
Yes Yes 1-250 1-60 1-60
Auto Reset ECS
Custom Event
Auto Reset
ECS Custom
Event
Yes Yes Never
Timer Event
Disabled
Never
Timer Event
Disabled
Never
Timer Event
Disabled
ECS Input ECS Input Yes Yes Latching
Non-Latching
Latching Latching
Event Priority CO Alarm No No Yes & No No No