151430-L8 System Operation
10-4
1. From the Main Menu, select 2 for Point Functions.
2. Press 8 to inhibit output group.
3. Use
the Up or Down arrow to select the group to be inhibited.
4. Press the right arrow to inhibit the group.
5. Press the right arrow again to enable the group.
10.4.3 View Event History
Use the View Event History feature to display events on LCD. From the Main Menu, press 3 to select Event
History. Events will begin displaying with most recent events first.
The panel can store up to 1000 events. When it reaches its 1000-event capacity, it will delete the oldest events to
make room for the new events as they occur. In networked setups, each panel stores up to 1000 of its own events.
When viewing Event History in the panel, the newest 500 events from every panel in the site will be displayed.
When using SKSS-2, all 1000 events from every panel in the network will be uploaded.
On multi-site displays, pressing ENTER or the right arrow brings you directly into View Event History and
allows you to view the Event History from every panel in each of the sites that the multi-site display is assigned
to.
10.4.3.1 To clear the event history
From the Installer menu select 1 for System Tests. From the test menu select 6 Clear History Buffer. In network
systems, this clears the History Buffer of all panels in the site.
10.4.4 Conduct a Fire Drill
1. From the Main Menu, press 1 for System Tests.
2. Press 1 for Fire Drill. You will be prompted to press ENTER.
3. The drill will begin immediately after you press ENTER.
4. Press any key to end the drill. (If you do not press any key to end the fire drill manually, it will time out auto-
matically after ten minutes.)
If a fire drill switch has been installed, activating the switch will begin the drill; deactivating the switch will end
the drill.
10.4.5 Conduct an Indicator Test
The indicator test checks the annunciator LEDs, PZT, and LCD display.
1. From the Main Menu, press 1 for System Tests.
2. Press 2 for Indicator Test. The system turns on each LED several times, beeping the PZT as it does so. At the
same time it scrolls each available character across the LCD. A problem is indicated if any of the following
occurs:
An LED does not turn on.
You do not hear a beep.
All four lines of the LCD are not full.
This test takes approximately 15 seconds to complete. You can press any key to end manually while the test is
still in progress. When the test ends, you will be returned to the <Test Menu>.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Farenhyt IFP-2000 and is the answer not in the manual?

Honeywell Farenhyt IFP-2000 Specifications

General IconGeneral
BrandHoneywell
ModelFarenhyt IFP-2000
CategoryConference System
LanguageEnglish

Related product manuals