Model IFP-2000/ECS Installation Manual 151430-L8
9-3
9.2.2 Adding a Module
To add a new hardware module to the system, follow these steps:
You must be in the Main Menu to perform this task. If necessary, enter the Installer Code.
1. Select 7 for Panel Programming.
2. Press 1 to enter module menu.
3. Press 2 to add a module.
4. From the next screen, select the number that corresponds to the type of module you are adding from the
<New Module Type> screen.
The screen will display “Adding module [#]...” for a few moments. You will be returned to the <New Mod-
ule Type> screen where you can add additional modules if desired.
You must save changes when you exit the Panel Programming or the new module will not be added.
Note: If you Add a Module that has not been physically connected, the panel will go into trouble after it reinitializes (when
you exit the Panel Programming). When the new module is attached, the trouble will correct itself automatically the
next time you power up the system.
9.2.3 Deleting a Module
To delete a module, follow these steps:
You must be in the Main Menu to perform this task. If necessary, enter the Installer Code.
1. Select 7 for Panel Programming.
2. Press 1 to enter module menu.
3. Press 3 to delete a module.
4. Select the module to be deleted.
5. A warning screen will display. If you want to proceed with deleting the module, select Yes. To cancel, select
No.
9.2.4 View Module List
To view a list of all modules, follow these steps:
You must be in the Main Menu to perform this task. If necessary, enter the Installer Code.
1. Select 7 for Panel Programming.
2. Press 1 to enter module menu.
3. Press 4 to view list. Use the Up or Down arrow to scroll though list.
9.3 Zone
Through the zone option in Panel Programming you can edit, add, delete, and view zone points. Selections made
here affect all detectors and switches in the zone. Up to 999 zones can be used in each panel.
Note: Adding a Zone or Deleting a Zone can only be done using SKSS-2 (Silent Knight Software Suite PN 5655).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Farenhyt IFP-2000 and is the answer not in the manual?

Honeywell Farenhyt IFP-2000 Specifications

General IconGeneral
BrandHoneywell
ModelFarenhyt IFP-2000
CategoryConference System
LanguageEnglish

Related product manuals