151430-L8 Programming Overview
8-2
need to manually change the switch type if manual pull is not correct.
The first JumpStart AutoProgramming creates one zone (Zone 1) and assigns all input points to Zone 1. Zone 1 is
mapped to Output Group 1.
8.2.2 Output Points
The first JumpStart AutoProgramming on a panel in default configuration creates three output groups and assigns
output circuits as follows:
Internal Power Supply Circuits 1-8:
Configured as Notification and assigned to Group 1.
Internal Power Supply Circuit 9 (Relay 1):
Assigned to Group 998.
Internal Power Supply Circuit 10 (Relay 2):
Assigned to Group 999.
Addressable output points (Relay modules):
All addressable relay devices will be configured as “Output Pt” (general purpose output point) and assigned to
Group 1.
Note: Relay output is constant even if the zone activating the relay is programmed with an output pattern.
8.2.3 Running JumpStart AutoProgramming
Run JumpStart AutoProgramming immediately after you have addressed and connected all input devices
(detectors, pull stations, and so on) and output devices (notification appliances, relays, and so on).
Note: If you need to install a few devices after you have run JumpStart AutoProgramming, you can install them
manually or run JumpStart again at a later time. JumpStart will keep user options, such as names, for de-
vices already installed. Follow instructions in Section 8 for configuration.
To run JumpStart AutoProgramming, follow these steps.
1. Press ENTER to view Main Menu.
2. Select 7 for Panel Programming. Enter Access Code.
3. Select 6 for JumpStart AutoProgramming.
4. The message “System will be shut down during JumpStart.” Press ENTER to accept.
5. When the “SLC Family” message appears, two options are presented; either IDP or SD. Select the appropri-
ate option based on the type of SLC devices the panel is using and press ENTER to accept.
6. A series of messages displays as JumpStart scans the system for expander modules and SLC loops for point
devices. This can take several minutes, depending on the number of devices attached.
7. If a Temp Programming Display is being used to initially setup an RPS-2000, a menu will appear for select-
ing to install the display or not. If the display is to stay in the system for normal annunciation, select “Yes,
Configure display for system.” Otherwise select “No, Display will be removed.” See Section 4.5.3.
8. When the message “Configuring System Done” displays, press any key to continue.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Farenhyt IFP-2000 and is the answer not in the manual?

Honeywell Farenhyt IFP-2000 Specifications

General IconGeneral
BrandHoneywell
ModelFarenhyt IFP-2000
CategoryConference System
LanguageEnglish

Related product manuals