EasyManuals Logo

Honeywell Farenhyt IFP-2000 User Manual

Honeywell Farenhyt IFP-2000
252 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #70 background imageLoading...
Page #70 background image
151430-L8 Control Panel Installation
4-30
2. Smoke power is supplied to each Class A loop as shown in Figure 4-39.
Figure 4-39 Class A 4-Wire Smoke Detector Connections
Note: In programming any point that uses multiple Flexput circuits are always referred to as the lowest Flexput
circuit number used. For example, Figure 4-39 uses Flexput circuits 1, 2, 3 together and 4, 5, 6 together.
In programming (1, 2, 3) would be referred to as point 1, and (4, 5, 6) would be referred to as point 4.
4.12.5 Auxiliary Power Installation
Flexput Circuits 1-8 on the control panel can be used as auxiliary power circuits. The three types of auxiliary
power available are:
Door Holder Power (see Section 4.12.5.1)
Constant Power (see Section 4.12.5.2)
Resettable Power (see Section 4.12.5.3)
Sounder Sync Power (see Section 4.12.5.4)
Auxiliary power circuits are power limited. Each circuit can source up to 3A (total current for all Flexput circuits
must not exceed 9.0 A in alarm, and 6A when used as constant auxiliary power in normal standby).
To install an auxiliary power circuit:
1. Wire the Flexput circuit(s) that will be used for auxiliary power. See Figure 4-40 for location of Flexput cir-
cuits.
Air Products
PAM-2
Model 160150
Supervision
Module
Air Products
PAM-2
Model 160150
Supervision
Module
Supervised
Power Limited
maximum
impedance per
circuit is 50

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Farenhyt IFP-2000 and is the answer not in the manual?

Honeywell Farenhyt IFP-2000 Specifications

General IconGeneral
BrandHoneywell
ModelFarenhyt IFP-2000
CategoryConference System
LanguageEnglish

Related product manuals