Model IFP-2000/ECS Installation Manual 151430-L8
6-3
switch setting. The system will be down as the panel needs to reboot in order to complete the transition.
When using the PC configuration software to program the panels, the Network Panel ID will be locked from
future editing. The only way to change it will be to restore defaults and use this menu again.
To Edit the Network Panel ID:
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select 6 for Network Programming.
3. Press 3 to enter the Edit Panel ID menu.
4. If the Network Panel ID is changed and valid, the system will ask you to confirm the change. If it is not cor-
rect, you can change the dip switches at this time.
5. Press up to select YES and press ENTER to confirm.
6.2.4 Computer Access
An installer at the panel site can initiate communications between the panel and a computer running the SKSS-2
(see also Section 10.4.14). In order for this communication to function properly, both the computer (running the
software) and the control panel must have matching computer access numbers and computer codes.
Before you program in this location you should know how your control panel will communicate with the
downloading computer, either through direct connect USB or via the phone lines (Internal Modem).
If the panel initiates the call to a downloading computer, a computer phone number must be programmed in the
computer access area. If the computer initiates the call, answering machine bypass may need to be selected (see
Section 9.6.2.7).
To program computer access information:
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select 6 for Network Programming.
3. Press 4 to enter the Computer Access menu.
4. Enter the computer access number (up to 6-digits), then press ENTER.
5. Enter the computer code, then press ENTER.
6. Enter the computer phone number, the panel will dial to connect to a downloading computer (up to 40-dig-
its), then press ENTER.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Farenhyt IFP-2000 and is the answer not in the manual?

Honeywell Farenhyt IFP-2000 Specifications

General IconGeneral
BrandHoneywell
ModelFarenhyt IFP-2000
CategoryConference System
LanguageEnglish

Related product manuals