151430-L8 Introduction
1-2
sites for multiple building applications.
Each building is referred to as a “site”. All panels in a site operate as a single panel.
Panels can be interconnected using a BUS or CLASS A (style 7) topology.
Panels can be connected cost effectively via shielded twisted pair copper wire within conduit when the
panels are located no more than 20 feet apart and within the same room.
Panels separated by more than 20 feet or located in multiple buildings use IFP-RPT network repeater
hardware to provide up to 3000 ft. of separation with twisted pair copper wire or up to 8dB loss of signal
separation for fiber optic cable. Both methods of panel connectivity can be used within the same networked
system.
The network architecture provides true peer to peer capability allowing network survivability for all
hardware that remains operational in the event of partial system failure.
1.1.3 Software Features
Advanced analog smoke detector features:
Three sensitivity settings (high, medium, low)
Automatic drift compensation
Maintenance alert region
Point status meets calibrated smoke test requirements for NFPA 72
Automatic day/night sensitivity adjustment
“JumpStart AutoProgramming” feature for easy programming
Non-volatile event history stores 1000 events per panel
A choice of output patterns available for notification outputs, including ANSI 3.41 temporal signal
Built-in synchronization appliance support for AMSECO, Gentex
®
, System Sensor
®
, and Wheelock
®
1.1.4 IFP-2000ECS Features
15 Recordable one minute messages that can be mapped to eight ECS buttons.
ECS messages can be selected as priority over fire.
Support of up to 15 ECS-RCU2000’s. The ECS-RCU2000 meets the requirements for an LOC.
Programmable trigger inputs from an external source, such as a Monaco system, to either the ECS-VCM,
ECS-RVM or 5880. Up to eight inputs available on the 5880 module.
Support for up to 16 SBUS addressable amplifiers using a combination of ECS-50W, ECS-125W, ECS-
INT50W or ECS-DUAL50W for a maximum of 2000 watts per system and up to 128 mappable speaker
circuits.
Support for dual channel and backup audio using the ECS-DUAL50W amplifier and ECS-50WBU back-up
amplifier.
Single enclosure for both Fire and Emergency Control System components.
1.2 About this Manual
This manual is intended to be a complete reference for all installation and operation tasks for the IFP-2000, IFP-
2000ECS*, IFP-2000HV, IFP-2000ECSHV**, RPS-2000, and RPS-2000HV.
Please let us know if the manual does not meet your needs in any way. We value your feedback!
* All references to IFP-2000 within this manual are applicable to the IFP-2000ECS.
** All references to IFP-2000HV within this manual are applicable to the IFP-2000ECSHV.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Farenhyt IFP-2000 and is the answer not in the manual?

Honeywell Farenhyt IFP-2000 Specifications

General IconGeneral
BrandHoneywell
ModelFarenhyt IFP-2000
CategoryConference System
LanguageEnglish

Related product manuals