151430-L8 Programming
9-14
9.5.2 Point Programming For Internal or External Power
Module (RPS-1000)
To program for an internal or external power module points:
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select 7 for Panel Programming.
3. Press 4 to enter point menu.
4. Press the or arrows to select the desired module. Refer to Section 8.6 for available choices, then
press ENTER.
5. Enter the number of the circuit or point you wish to edit, then press ENTER.
6. Select the type by pressing the or arrows, then press ENTER.
7. Select the function by pressing the or arrows, then press ENTER.
8. If the point supports latching press the or arrows to select latching or non-latching, then press
ENTER.
9. Select the zone or group by pressing the or arrows, then press ENTER.
10. If the point supports not being supervised, press the or arrows to select supervised or non-super-
vised, then press ENTER.
11. Press ENTER to edit point name. See Appendix B.
Or
Press the right arrow to skip point name edit.
12. Repeat Steps 1 through 16 for all circuits.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Farenhyt IFP-2000 and is the answer not in the manual?

Honeywell Farenhyt IFP-2000 Specifications

General IconGeneral
BrandHoneywell
ModelFarenhyt IFP-2000
CategoryConference System
LanguageEnglish

Related product manuals