EasyManua.ls Logo

Honeywell Farenhyt IFP-2000 - Point Programming For 5880;5865 Modules

Honeywell Farenhyt IFP-2000
252 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
151430-L8 Programming
9-16
9.5.3 Point Programming For 5880/5865 Modules
To program the 5880/5865 module output points:
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select 7 for Panel Programming.
3. Press 4 to enter point menu.
4. Press the Up or Down arrows to select the desired module. Refer to Section 8.6 for available choices. Then
press ENTER.
Figure 9-5 Programming Points as Outputs for the 5880 Module
Figure 9-6 Programming Points as Inputs for the 5880 Module
5. Enter the point number, then press ENTER.
6. Press the Up or Down arrows to select the type (notification or unused)., then press ENTER.
7. Press the Up or Down arrows to select the desired group., then press ENTER.
8. Press ENTER to edit point name. See Appendix B.
Or
Press the right arrow to skip point name edit.
9. Repeat Steps 1 through 8 for all output points.
10. To use 5880 as Input point, Enter point number 41 - 48. (See Figure 9-6 on page 16). Then press ENTER.
11. Press the Up or Down arrows to select type (switch or unused), then press ENTER.
12. Press the Up or Down arrows to select the desired function. (See Figure 9-5 on page 19), then press ENTER.
13. If the point supports latching press the Up or Down arrows to select latching or non-latching, then press
ENTER.
14. Press the Up or Down arrows to select the desired group/zone, then press ENTER.
15. Edit point name Or Press the right arrow to skip module name edit.
16. Repeat steps 10 through 15 for all input points.
Enter Point
Select NOTIF
or Unused
Select an output Group
for this Zone/Group
Select a name
for the Point
Select Switch
or Unused
Select Function

Table of Contents