151430-L8 Programming
9-4
9.3.1 Edit Zone
Features that can be edited through the edit zone option are, edit zone name, zone properties (which includes
zone type and detector sensitivity), and zone accessory options.
To edit a zone, follow these steps:
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select 7 for Panel Programming.
3. Press 2 to enter zone menu.
4. Press 1 to edit a zone.
5. Enter the zone number, then press ENTER.
9.3.1.1 Edit Zone Name
6. Press 1 to edit the selected zone name.
You can use words to display a descriptive name for a zone.
Note: See Appendix B for editing names.
9.3.1.2 Edit Zone Properties
Zone properties consist of alarm delay characteristics, heat detector sensitivity, and smoke detector sensitivity.
1. Do steps 1 through 5 of Section 9.3.1.
2. Press 2 to edit the properties of the selected zone.
Detection type is selected from this
screen (see Table 9-1).
Select temperature that will cause heat
detectors in this zone to go into alarm.
Range: 135-190°F (IDP)
Range: 135-150°F (SD)
Zone # being
programmed
Select sensitivity Low,
Medium, or High