Model IFP-2000/ECS Installation Manual 151430-L8
9-25
8. Enter the number of hours before a low AC report will be sent to the central station, then press ENTER.
Refer to Figure 9-14.
9.6.5.4 Change AC Line Frequency
The panel’s AC line frequency is selectable for 50, 60 Hz, or Neither. AC Frequency feature dictates how the
control panel will calculate time based on the AC line frequency used in the installation site. The “Neither”
option can be used in areas where the AC line frequency is not dependable and you want the panel to calculate
time from the internal crystal. The internal crystal is not as accurate as the AC power source and either 60 Hz or
50 Hz should normally be selected. The panel defaults to the 60 Hz selection.
To change the AC line frequency:
9. Select 50Hz, 60Hz or Neither, by pressing the Up or Down arrow, then press ENTER.
9.6.5.5 Clock Display Format (AM/PM or Military)
To change the system clock display format:
10. Select AMPM (for AM/PM display format) or MIL (for military or 24 hr display format) by pressing the Up
or Down arrow, then press ENTER.
9.6.6 Miscellaneous Options
Through this programming option you can do strobe synchronization during silence, auto display event, repeater
installed, and ports of repeater used.
To edit Miscellaneous options:
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select 7 for Panel Programming.
3. Select 5 for System Options.
4. Select 5 for Miscellaneous Options.
9.6.6.1 Strobes Active when Silenced
When “SYNC Strobe:” is selected as Y (Yes), the strobes will continue to flash when the system is silenced and
will stop flashing when the system is reset.
Note: The “SYNC Strobe:” only functions with outputs that use a synchronized output pattern.
5. Press the Up or Down arrow to toggle this selection between Y (Yes) or N (No).
6. Press the right arrow
or ENTER to make your selection and move to the next programming option.
9.6.6.2 Auto Display Events
When this feature is programmed Y (Yes), the highest priority event of the system in control will automatically
display on the control panel and remote annunciators after there has been no activity on any system touch pad for
two minutes.
7. Press the Up or Down arrow to toggle this selection between Y (Yes) or N (No).
8. Press the right arrow
or ENTER to make your selection and move to the next programming option.
9.6.6.3 IFP-RPT Repeater Installed
When the “Repeater Installed” option is programmed Y (Yes), the panel will supervise the IFP-RPT Repeater.
Set N (No) when an IFP-RPT Repeater is not installed.
9. Press the Up or Down arrow to toggle this selection between Y (Yes) or N (No).