151430-L8 Reporting
12-6
System-based AUX2 switch alarm UA 2000 UANN002000 1 140 02 000
System-based AUX2 switch alarm
restore
UH 2000 UHNN002000 3 140 02 000
System-based AUX2 switch trou-
ble
UT 2000 UTNN002000 1 373 02 000
System-based AUX2 switch trou-
ble restore
UJ 2000 UJNN002000 3 373 02 000
Voice Aux ECS 1 Alarm UA 3 UANN003000 1 171 00 000
Voice Aux ECS 1 Alarm Restore UH 3 UHNN003000 3 171 00 000
Voice Aux ECS 2 Alarm UA 4 UANN004000 1 172 00 000
Voice Aux ECS 2 Alarm Restore UH 4 UHNN004000 3 172 00 000
Voice Aux ECS 3 Alarm UA 5 UANN005000 1 173 00 000
Voice Aux ECS 3 Alarm Restore UH 5 UHNN005000 3 173 00 000
Voice Aux ECS 4 Alarm UA 6 UANN006000 1 174 00 000
Voice Aux ECS 4 Alarm Restore UH 6 UHNN006000 3 174 00 000
Water flow switch alarm SA Zone # SANN000ZZZ 1 113 00 Zone #
Water flow switch alarm Restore SH Zone # SHNN000ZZZ 3 113 00 Zone #
Water flow switch trouble ST Zone # STNN000ZZZ 1 373 00 Zone #
Water flow switch trouble Restore SJ Zone # SJNN000ZZZ 3 373 00 Zone #
Zone-based AUX1 switch alarm UA Zone # +
1000
UANN001ZZZ 1 140 01 Zone #
Zone-based AUX1 switch alarm
restore
UH Zone # +
1000
UHNN001ZZZ 3 140 01 Zone #
Zone-based AUX1 switch trouble UT Zone # +
1000
UTNN001ZZZ 1 373 01 Zone #
Zone-based AUX1 switch trouble
restore
UJ Zone # +
1000
UJNN001ZZZ 3 373 01 Zone #
Zone-based AUX2 switch alarm UA Zone # +
2000
UANN002ZZZ 1 140 02 Zone #
Zone-based AUX2 switch alarm
restore
UH Zone # +
2000
UHNN002ZZZ 3 140 02 Zone #
Zone-based AUX2 switch trouble UT Zone # +
2000
UTNN002ZZZ 1 373 02 Zone #
Zone-based AUX2 switch trouble
restore
UJ Zone # +
2000
UJNN002ZZZ 3 373 02 Zone #
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier SIA IFP-2000
Event Description
Module ID
# (If Any)
SIA
Event
Codes
Parameter
Fixed Length
Format NN -
panel ID
XX- SBUS ID
ZZZ - Zone #
PPPP- Point #
GGG- Group #
E - Emergency #
RRRR- Receiver #
Qualifier
Event
Code
Group # Contact #

Table of Contents