151430-L8 Reporting
12-8
ECS Alarm # Point Trouble Re-
store
pi Exp. ID QJ Point # QJNNXXPPPP 3 242 Exp. ID Point #
ECS Alarm # Point Disabled pi Exp. ID QB Point # QBNNXXPPPP 1 243 Exp. ID Point #
ECS Alarm # Point Enabled pi Exp. ID QU Point # QUNNXXPPPP 3 243 Exp. ID Point #
ECS Supervisory/Tamper Alarm pi Exp. ID QS Point # QSNNXXPPPP 1 241 Exp. ID Point #
ECS Supervisory/Tamper Alarm
Restore
pi Exp. ID QR Point # QRNNXXPPPP 3 241 Exp. ID Point #
ECS Supervisory/Tamper Trouble pi Exp. ID QT Point # QTNNXXPPPP 1 242 Exp. ID Point #
ECS Supervisory/Tamper Trouble
Restore
pi Exp. ID QJ Point # QJNNXXPPPP 3 242 Exp. ID Point #
ECS Supervisory/Tamper Dis-
abled
pi Exp. ID QB Point # QBNNXXPPPP 1 243 Exp. ID Point #
ECS Supervisory/Tamper Enabled pi Exp. ID QU Point # QUNNXXPPPP 3 243 Exp. ID Point #
ECS NAC Trouble pi Exp. ID QT Point # QTNNXXPPPP 1 320 Exp. ID Point #
ECS NAC Trouble Restored pi Exp. ID QJ Point # QJNNXXPPPP 3 320 Exp. ID Point #
ECS Control Circuit Trouble pi Exp. ID QT Point # QTNNXXPPPP 1 320 Exp. ID Point #
ECS Control Circuit Trouble Re-
stored
pi Exp. ID QJ Point # QJNNXXPPPP 3 320 Exp. ID Point #
ECS Relay Trouble pi Exp. ID QT Point # QTNNXXPPPP 1 320 Exp. ID Point #
ECS Relay Trouble Restored pi Exp. ID QJ Point # QJNNXXPPPP 3 320 Exp. ID Point #
ECS Notification Trouble pi Exp. ID QT Point # QTNNXXPPPP 1 320 Exp. ID Point #
ECS Notification Trouble Restored pi Exp. ID QJ Point # QJNNXXPPPP 3 320 Exp. ID Point #
External Reset/Silence/Fire Drill
switch disabled
pi Exp. ID UB Point # UBNNXXPPPP 1 571 Exp. ID Point #
External Reset/Silence/Fire Drill
switch enabled
pi Exp. ID UU Point # UUNNXXPPPP 3 571 Exp. ID Point #
External Reset/Silence/Fire Drill
switch trouble
pi Exp. ID UT Point # UTNNXXPPPP 1 373 Exp. ID Point #
External Reset/Silence/Fire Drill
switch trouble restore
pi Exp. ID UJ Point # UJNNXXPPPP 3 373 Exp. ID Point #
Interlock switch alarm (Water Re-
lease Zone)
pi Exp. ID FA Point # FANNXXPPPP 1 110 Exp. ID Point #
Interlock switch alarm restore (Wa-
ter Release Zone)
pi Exp. ID FH Point # FHNNXXPPPP 3 110 Exp. ID Point #
Interlock switch disabled pi Exp. ID FB Point # FBNNXXPPPP 1 571 Exp. ID Point #
Interlock switch enabled pi Exp. ID FU Point # FUNNXXPPPP 3 571 Exp. ID Point #
Interlock switch trouble (Water Re-
lease Zone)
pi Exp. ID FT Point # FTNNXXPPPP 1 373 Exp. ID Point #
Interlock switch trouble restore
(Water Release Zone)
pi Exp. ID FJ Point # FJNNXXPPPP 3 373 Exp. ID Point #
LOC Mic Activated ECS Alarm pi Exp. ID QA 0 QANNXX0000 1 220 Exp. ID 000
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier SIA IFP-2000
Event Description
Module ID
# (If Any)
SIA
Event
Codes
Parameter
Fixed Length
Format NN -
panel ID
XX- SBUS ID
ZZZ - Zone #
PPPP- Point #
GGG- Group #
E - Emergency #
RRRR- Receiver #
Qualifier
Event
Code
Group # Contact #