151430-L8 Reporting
12-10
Supervisory/Tamper Alarm pi Exp. ID FS Point # FSNNXXPPPP 1 200 Exp. ID Point #
Supervisory/Tamper Alarm
Restore
pi Exp. ID FR Point # FRNNXXPPPP 3 200 Exp. ID Point #
Supervisory/Tamper point dis-
abled
pi Exp. ID FB Point # FBNNXXPPPP 1 571 Exp. ID Point #
Supervisory/Tamper point enabled pi Exp. ID FU Point # FUNNXXPPPP 3 571 Exp. ID Point #
Supervisory/Tamper point trouble pi Exp. ID FT Point # FTNNXXPPPP 1 373 Exp. ID Point #
Supervisory/Tamper point trouble
restore
pi Exp. ID FJ Point # FJNNXXPPPP 3 373 Exp. ID Point #
System-based AUX1 switch alarm pi Exp. ID UA Point # UANNXXPPPP 1 140 Exp. ID Point #
System-based AUX1 switch alarm
restore
pi Exp. ID UH Point # UHNNXXPPPP 3 140 Exp. ID Point #
System-based AUX1 switch dis-
abled
pi Exp. ID UB Point # UBNNXXPPPP 1 571 Exp. ID Point #
System-based AUX1 switch en-
abled
pi Exp. ID UU Point # UUNNXXPPPP 3 571 Exp. ID Point #
System-based AUX1 switch trou-
ble
pi Exp. ID UT Point # UTNNXXPPPP 1 373 Exp. ID Point #
System-based AUX1 switch trou-
ble
restore
pi Exp. ID UJ Point # UJNNXXPPPP 3 373 Exp. ID Point #
System-based AUX2 switch alarm pi Exp. ID UA Point # UANNXXPPPP 1 140 Exp. ID Point #
System-based AUX2 switch alarm
restore
pi Exp. ID UH Point # UHNNXXPPPP 3 140 Exp. ID Point #
System-based AUX2 switch dis-
abled
pi Exp. ID UB Point # UBNNXXPPPP 1 571 Exp. ID Point #
System-based AUX2 switch en-
abled
pi Exp. ID UU Point # UUNNXXPPPP 3 571 Exp. ID Point #
System-based AUX2 switch
trouble
pi Exp. ID UT Point # UTNNXXPPPP 1 373 Exp. ID Point #
System-based AUX2 switch
trouble restore
pi Exp. ID UJ Point # UJNNXXPPPP 3 373 Exp. ID Point #
Voice Aux ECS 1 Point Alarm pi Exp. ID UA (3PPP) PPP
- Point #
UANNXX3PPP 1 171 Exp. ID Point #
Voice Aux ECS 1 Point Alarm
Restore
pi Exp. ID UH (3PPP) PPP
- Point #
UHNNXX3PPP 3 171 Exp. ID Point #
Voice Aux ECS 2 Point Alarm pi Exp. ID UA (4PPP) PPP
- Point #
UANNXX4PPP 1 172 Exp. ID Point #
Voice Aux ECS 2 Point Alarm
Restore
pi Exp. ID UH (4PPP) PPP
- Point #
UHNNXX4PPP 3 172 Exp. ID Point #
Voice Aux ECS 3 Point Alarm pi Exp. ID UA (5PPP) PPP
- Point #
UANNXX5PPP 1 173 Exp. ID Point #
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier SIA IFP-2000
Event Description
Module ID
# (If Any)
SIA
Event
Codes
Parameter
Fixed Length
Format NN -
panel ID
XX- SBUS ID
ZZZ - Zone #
PPPP- Point #
GGG- Group #
E - Emergency #
RRRR- Receiver #
Qualifier
Event
Code
Group # Contact #