151430-L8 Before You Begin Installation
3-10
IDP-Control-6
(159 max/loop
& 636 max/
panel)
1
SLC Standby 2.25 mA mA
Alarm: 2.25 mA mA
Aux Pwr Standby 8 mA mA
Alarm: 20 mA mA
IDP-Relay Standby/Alarm: .255 mA mA mA
IDP-Relay-6 Standby/Alarm: 1.45 mA mA mA
IDP-RelayMon-2
Standby: 1.3 mA mA
Alarm: 24 mA mA
IDP-Zone
Aux Pwr Standby 12 mA mA
Alarm: 90 mA mA
SLC Standby/Alarm .27 mA mA mA
IDP-Zone-6
Aux Pwr Standby 50 mA mA
Alarm: 70 mA mA
SLC Standby/Alarm 2 mA mA mA
SLC Accessories
B200SR/IV Sounder Base
(159 max/loop
& 636 max/
panel)
Aux Pwr Standby: .5 mA mA
Alarm: 35 mA mA
SLC Standby .3 mA mA
B200S/IV Intelligent Sounder Base
Aux Pwr Standby: .5 mA mA
Alarm: (high vol) 35 mA mA
SLC Standby .3 mA mA
B200SR-LF/IV Low Frequency
Sounder Base
Aux Pwr Standby: 1 mA mA
Alarm: 125 mA mA
B200S-LF/IV Low Frequency
Sounder Base
Aux Pwr Standby .55 mA mA
Alarm (high vol) 140 mA mA
SLC Standby .30 mA mA
B224RB/IV Relay Base Standby/Alarm: .5 mA mA mA
RT151/151 KEY Alarm: 7.5 mA
mA
RA100Z Alarm: 10 mA
mA
SLC Isolator Devices
IDP-ISO (Isolator Module)
(318 max/loop
& 636 max/
panel)
Standby/Alarm: .45 mA mA mA
ISO-6 (6 Fault Isolator Module)
Standby: (per circuit) .45 mA mA
Alarm: (per circuit) 17 mA mA
B224BI/IV Isolator Base Standby/Alarm: 0.5 mA mA mA
Accessories Modules
5815XL SLC Expander
(63 max)
4
Standby: 55 mA mA
Alarm: 125mA mA
RA-2000 Remote Fire Alarm
Annunciator
(63 max)
4
Standby: 25 mA mA
Alarm: 50 mA mA
5824 Serial/Parallel Module (2 max.) Standby/Alarm: 45 mA mA mA
5496 Intelligent Power Module
(63 max)
4
Standby/Alarm: 10 mA mA mA
RPS-1000 IntelliKnight Power
Module
(63 max)
4
Standby/Alarm: 10 mA mA mA
Table 3-1: Current Draw Worksheet for IDP SLC Devices
Device # of Devices Current per Device
Standby
Current
Alarm
Current