4. Installation
4.2. Installing CIOM-A Fieldbus Interface Module TC-FFIF01
108 Experion PKS Series A Fieldbus Interface Module User's Guide R400
Honeywell July 2010
Step Action
If Cable Number is:
TC-FFC010
TC-FFC025
TC-FFC050
TC-FFC100
Then, Cable Length is:
1 m (3 ft)
2.5 m (8 ft)
5 m (16 ft)
10 m (33 ft)
2
Align the right-hand cable plug on the RTP cable with the RTP connector
available through a cutout in the CIOM-A FIM door, and fully seat the RTP
cable plug into the connector.
3
Route the cable to the RTP.
4
Repeat Steps 1 to 3 for each CIOM-A FIM, as required.
5
Go to the next procedure Loading FIM firmware, if required.
Loading FIM firmware
ATTENTION
If the FIM is not installed and pre-configured by the factory, users must load
the FIM's firmware to make it fully operational. This is also true for any
replacement FIM ordered separately from the factory.
Once the Control hardware is installed and system communications are established, refer
to Loading FIM firmware
in Appendix G for a procedure to update the FIM's firmware.
The procedure for loading the FIM's firmware is similar to the one used for loading the
CPM's personality image.
TIP
The boot and personality image files are fimboot.nvs and fimrex.nvs,
respectively, and they are at this directory location: c:\Program
Files\Honeywell\Experion PKS\Engineering Tools\system\firmware\FIM