11. Appendix B
11.1. Standard Function Block Parameters
R400 Experion PKS Series A Fieldbus Interface Module User's Guide 445
July 2010 Honeywell
Remarks
Read Only
FSTATE_TIME
Classification
Simple Variable
Description
Represents the reaction time in seconds from the detection
of a failure at the output block remote set point to the output
block action, if the condition still exists.
FF Data Type
Float
Range
Positive
Usage
C/Contained
Length
4
Valid Views
VIEW_4
Storage
Static
Remarks
FSTATE_VAL
Classification
Simple Variable
Description
Defines the preset analog set point to use when a failure
occurs. Value is ignored, if the IO_OPTS Fault state to
value option is false.
FF Data Type
Float
Range
PV_SCALE +/- 10 percent
Usage
C/Contained
Length
4
Valid Views
VIEW_4
Storage
Static
Remarks