6. Operation
6.3. Monitoring Fieldbus Functions Through Monitoring Tab
264 Experion PKS Series A Fieldbus Interface Module User's Guide R400
Honeywell July 2010
Step Action Result
TIP
The alternative to a restart is manually cycling power to the fieldbus device.
10
Click Yes to restart the fieldbus device.
Fieldbus device operational class
changes to Basic after restart.
TIP
You can confirm the change by calling up the device's Parameters form and checking
that BASIC appears in the DL Operational Functional Class field on the Network
Management (Basic) tab.
11
This completes the procedure. Repeat
the procedure for another device, as
applicable.
Checking live list and interacting with uncommissioned devices
Use t
he following procedure to check the link for devices that are added to the Live List
as uncommissioned. The illustrations used are for example purposes only and may differ
from the actual forms that appear in your system.
CAUTION
Be sure you review the Guidelines for adding fieldbus device to
"live"/operating Link in the next section before adding an uncommissioned
fieldbus device to an in-service Link.
Step Action Result
1
Check the Link icon for the presence of
an asterisk
.
An asterisk signals that an
uncommissioned device has been added
to the link.