5. Configuration
5.7. Block Offnet Diagnostic Alarm
234 Experion PKS Series A Fieldbus Interface Module User's Guide R400
Honeywell July 2010
Step Action
3
Perform through steps 4 to 7 of the section Configuring/creating a condition
.
ATTENTION
You can delete an alarm condition, based on the required alarms to be
generated.
To delete a condition in the Condition Listing tab
a) Select the condition to click Delete.
b) Click Yes to confirm the deletion of the selected condition or
press Delete on the keyboard.
5.7 Block Offnet Diagnostic Alarm
In R400 and later, a Fieldbus function block can optionally be configured to generate a
high-priority alarm, when the device containing the block is disconnected from the
network. This is accomplished with the introduction of a new parameter
OFFNETALM_ENABLED. When this parameter is set to “True” and if the device is off