5. Configuration 
5.5. Loading Components Online 
R400  Experion PKS Series A Fieldbus Interface Module User's Guide  211 
July 2010  Honeywell 
Step Action  Result 
5 
Confirm that CIOM-A FIM icon now 
appears in Monitoring tab. Click 
 plus 
sign for CIOM-A FIM icon.  
Opens directory and exposes LINK icons. 
 
 
 
6 
This completes CIOM-A FIM load. Go to 
the next section Matching 
uncommissioned device to project device 
or vice versa. 
 
 
 
Matching uncommissioned device to project device or vice versa 
 
 
TIP 
If you are running R210 or greater software, the FIM will detect when an 
uncommissioned (new) device is added to the link, prepare it for joining the 
link, and define the device as an uncommissioned Basic device. In this case, 
you can skip the following procedure.  
 
Use the following procedure to initiate the device matching function to conveniently 
match uncommissioned fieldbus devices with their counterpart devices in the Project tab 
or project devices. It is best to match devices before you download the fieldbus device 
from Project to the Link.  
 
Step Action  Result 
1 
If Link is inactive (blue icon), go to Step 
2.  
If Link is active (green icon), go to Step 6. 
Link must be active to detect 
uncomminssioned devices on it.