3. Fieldbus Integration With Experion System 
3.1. Overview 
R400  Experion PKS Series A Fieldbus Interface Module User's Guide  35 
July 2010  Honeywell 
 
Redundant Fieldbus integrated architecture for CIOM-A FIM 
The follo
wing figure shows a sample redundant fieldbus architecture using a pair of 
CIOM-A Fieldbus Interface Modules (FIMs) and Redundancy Modules (RMs) in a 
redundant C200 Controller and a redundant remote I/O chassis configuration. The FIM 
serves as the communication gateway between the Supervisory ControlNet and/or I/O 
ControlNet network and the Foundation Fieldbus H1 communications medium. It 
includes a redundant Remote Termination Panel (RTP) for connecting and powering up 
to two fieldbus H1 links. The illustration in the following figure is for example purposes 
only to show the possible architectural variations for a redundant fieldbus application.  
 
 
ATTENTION 
No chassis I/O modules are permitted in a remote I/O chassis pair configured 
for redundant fieldbus support. Only redundancy compliant modules can be 
used in a Redundant Chassis Pair configuration. The same is true for the 
redundant Controller chassis.