8. Maintenance, Checkout, and Calibration
8.5. Upgrading Firmware in Uncommissioned Device
R400 Experion PKS Series A Fieldbus Interface Module User's Guide 329
July 2010 Honeywell
devices on the link off control before upgrading firmware in a ST3000,
STT35F, or LX1400 device.
Step Action Result
1
Double-click the uncommissioned device
icon .
Opens the LINK Parameters form with
the Uncommissioned Devices tab open.
This illustration is for example purposes
only.
TIP
If the Load Firmware button is inactive (grayed out), try changing the device address to
a lower number in the 30 to 40 range.