11. Appendix B
11.1. Standard Function Block Parameters
R400 Experion PKS Series A Fieldbus Interface Module User's Guide 427
July 2010 Honeywell
Storage
Dynamic
Remarks
BLOCK_ERR.DISABLED
Classification
Description
Enables you to disable individual block errors.
FF Data Type
Bitstring
Range
Usage
C/Contained
Length
Valid Views
Dynamic
Storage
Remarks
For the blocks such as AI block configured in Control
Modules, when an inactive block error is disabled and
if the block error turns active, the Alarm Display will
not display the alarm and the Event Summary will not
display the alarm event. For the devices only blocks
such as, Resource or Transducer blocks, block error
alarm appearance in the Alarm Display or System
Status Display is affected.
Regardless of disabling, the individual block error
status is displayed on the block’s Maintenance tab.
When an active block error is disabled, the Alarm
Display or System Status Display alarm returns to
normal, and Event Summary displays the alarm action
as OK.
In the Alarm Display or System Status Display,
when you acknowledge block error alarms that have
returned to normal, the alarms disappear and Event
Summary displays the acknowledged alarms.
When the disable is removed for an active block error,
the Alarm Display or System Status Display displays
the alarm as active and Event Summary receives the
event for that particular alarm.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Series A and is the answer not in the manual?

Honeywell Series A Specifications

General IconGeneral
BrandHoneywell
ModelSeries A
CategoryRecording Equipment
LanguageEnglish

Related product manuals