10. Appendix A 
10.2. Standard Function Blocks 
384  Experion PKS Series A Fieldbus Interface Module User's Guide   R400 
 Honeywell July 2010 
Fieldbus
AI Block
PID Block
AO Block
Device 1
Device 2
 
 
Figure 38  Using Function Blocks in fieldbus devices to form a control 
loop. 
 
About modes of operation 
Every
 Function block includes a mode parameter with configured permitted modes. This 
structured parameter is composed of the actual mode, the target mode, the permitted 
mode, and the normal mode. The normal mode is the desired operating mode. The actual 
mode reflects the mode used during block execution. The target mode may be set and 
monitored through the mode parameter. The permitted mode defines the allowable target 
mode settings. The following table provides a summary of the available modes of 
operation and their effect on operation.  
 
Mode Abbreviation  Operation Effect 
Out of Service  OOS 
The block is not being evaluated. The output 
is maintained at the last value, an assigned 
fault state value -last value or configured 
fault state value. Set Point is maintained at 
last value.  
Initialization Manual  IMan 
The block output is being set in response to 
the back-calculation input parameter status.