8. Maintenance, Checkout, and Calibration
8.2. Unlike Device Replacement Report
R400 Experion PKS Series A Fieldbus Interface Module User's Guide 317
July 2010 Honeywell
Step Action Result
44
Wait for the load to complete and check
that the CM is restored in Monitoring tab.
Return to normal operation.
TIP
It is a good idea to do an Upload followed by an Update to Project for the fieldbus
device and the CMs after a replacement procedure.
45
This completes the device replacement
with different block type procedure.
8.2 Unlike Device Replacement Report
With R400, Unlike Device Replacement (UDR) Report can be generated to view
information about the device to be replaced and the control modules that are affected due
to replacement of the failed device.