5. Configuration 
5.4. Configuring Fieldbus Components In a Control Strategy 
154  Experion PKS Series A Fieldbus Interface Module User's Guide   R400 
 Honeywell July 2010 
Step Action  Result 
4 
Repeat Step 3 for device LX102.  
Device is added to the Assigned Devices 
list box with the assign state icon.  
 
 
 
 
TIP 
If duplicate address error message appears, go to the next section Checking device 
configuration for details on changing the device's network node address. It is possible 
for device addresses to be set to the same default value of 20.  
5 
Click Close.  Closes the dialog box.  
6 
Repeat the procedure to assign other 
devices or go to the next section 
Checking device configuration 
 
 
Checking device configuration 
Use t
he following procedure to check the configuration of a selected fieldbus device in 
the Project tab. This procedure assumes that the device has been assigned to a Link.