7. Fieldbus Device Commissioning
7.2. Connecting Devices
280 Experion PKS Series A Fieldbus Interface Module User's Guide R400
Honeywell July 2010
Stage Funtion Completed
Adding CIOM-A FIM block to Project
Loading a CIOM-A FIM and its Links
3
Was FIM download successful?
NO > Go to Stage 4
YES > Go to Stage 7
4
Is chassis and CIOM-A FIM powered?
NO > Go to Stage 5
YES > Go to Stage 6
5
Be sure required voltage is present at the power supply and it is
turned On.
Replace power supply, if required.
Return to Stage 2.
6
Verify network connections.
Replace FIM, if required.
Return to Stage 2.
7
Measure and establish H1 segment baseline with Fluke
Scopemeter and Relcom FTB-3 or equivalent equipment.
Go to Stage 8 in the next section Connecting Devices
7.2 Connecting Devices
Stage Funtion Completed
8
Connect the next device.
References:
Wiring
9
Does device appear on link?
NO > Go to Stage 10