Figure 42  Functional schematic for Control Selector function block.  
 
 
Description 
The Control Selector function block accepts input from up 
to three control signals and selects one for output based on 
the SEL_TYPE setting of High, Middle, or Low. A functional 
schematic of the block is shown in the previous illustration 
for reference. 
Function Notes 
    All inputs must have the same scaling as OUT, since 
any one can be selected for OUT.  
    Supports Out of Service (OOS), Initialization Manual 
(IMan) Local Override (LO), Manual (Man), and 
Automatic (Auto) modes.  
    If an input has a sub-status of Do Not Select, it will not 
be selected.  
    Three separate back calculation outputs 
(BKCAL_SEL_1, 2, 3) are available - one for each