11. Appendix B 
11.1. Standard Function Block Parameters 
R400  Experion PKS Series A Fieldbus Interface Module User's Guide  473 
July 2010  Honeywell 
2: Restart Resource  
3: Restart with Defaults 
4: Restart Processor 
Usage 
C/Contained 
Length 
1 
Valid Views 
 
Storage 
Dynamic 
Remarks 
Changing this parameter, may be fatal to communication. 
Note that the Restart with Defaults function restarts the 
fieldbus device with factory default values instead of 
Experion ones. To restore Experion default values, re-load 
the device block through Control Builder with associated 
blocks set for Full instead of Partial Load.  
 
ROUT_IN 
 
Classification 
Record 
Description 
Represents target output and status provided by a host to a 
control block for use as the block's output in ROUT mode.  
FF Data Type 
DS-65 
Range 
 
Usage 
C/Remote-Output In 
Length 
5 
Valid Views 
VIEW_3 
Storage 
Dynamic 
Remarks 
The data type consists of the value and status of floating 
point parameters that are Inputs or Outputs. It uses the 
following two elements.  
    1 Status 
    2 Value