3. Fieldbus Integration With Experion System 
3.7. CIOM-A FIM Redundancy Functionality 
84  Experion PKS Series A Fieldbus Interface Module User's Guide   R400 
 Honeywell July 2010 
For this Switchover Consideration . . .   FIM Redundancy Operation . . .  
Online Address Swap 
Swaps network addresses between 
Primary and Secondary FIM links. The 
link addresses are 16 for the Primary FIM 
and 17 for the Secondary FIM. During 
switchover or swap, the Secondary FIM 
becomes the Primary FIM and assumes 
address 16, while the Primary FIM 
becomes the Secondary FIM and 
assumes address 17 or is Disqualified. 
The Primary FIM continues Link Master 
operations.   
 
 
Switchover versus fieldbus network activities 
Th
e following table summarizes how given fieldbus network activities behave during a 
switchover.  
 
 
ATTENTION 
Depending upon the link communication load, number of devices, and type of 
parameter, fresh viewed data from field devices may be delayed for up to 20 
seconds during a CIOM-A FIM chassis switchover. This does not apply to 
control data. 
 
 
If Network Activity Is . . .   Then, Behavior During Switchover Is . . .  
Link Maintenance 
Since Secondary FIM link is a backup Link Active 
Scheduler (LAS), it resumes network management 
activities as soon as it detects that the old Primary 
FIM is no longer there. 
Both Primary and Secondary FIM links have the 
same knowledge of current time. When new 
Primary takes over as acting Link Master, it also 
becomes acting time publisher.  
System Management 
Operations 
Any System Management operation that is in 
progress is interrupted. For example, the new 
Primary does not know anything about pending 
change tag or address operation. As a result, 
device whose address or tag is being changed will 
timeout and abort the operation.