16. Appendix G
16.1. Loading CIOM-A FIM firmware
R400 Experion PKS Series A Fieldbus Interface Module User's Guide 525
July 2010 Honeywell
Step Action Result
6
Check the boot version (BV) and
application (personality) version (AV)
listed on the face of the CIOM-A FIM
(FFIF01) module graphic. This
illustration is for example purposes only.
If the version numbers shown are colored
green, they are the correct ones for your
current system software version. If they
are colored red, they need to be updated.
7
If firmware versions are correct (green),
click NetworkTools->Exit to close the
utility and quit this procedure.
If firmware versions are wrong (red), go
to the next procedure Loading Boot
code to continue.
Loading Boot code
Th
is procedure assumes that you have launched Ntools and determined that the CIOM-A
FIM firmware needs to be updated.
Step Action Result