R400   Experion PKS Series A Fieldbus Interface Module User's Guide  419 
July 2010  Honeywell   
11. Appendix B 
11.1  Standard Function Block Parameters 
ACK_OPTION 
 
Classification 
Simple Variable 
Description 
Selects whether alarms associated with the block will be 
automatically acknowledged. 
FF Data Type 
Bit String 
Range 
1: Unacknowledge 
Usage 
C/Contained 
Length 
2 
Valid Views 
VIEW_4 
Storage 
Static 
Remarks 
Initial value is 0 
 
ALARM_HYS 
 
Classification 
Simple Variable 
Description 
Defines the amount of change a PV value must attain within 
the alarm limits before the alarm condition clears.   
FF Data Type 
Float 
Range 
0 to 50 percent of PV span 
Usage 
C/Contained 
Length 
4 
Valid Views 
VIEW_4 
Storage 
Static 
Remarks 
Initial value is 0.5 percent 
 