11. Appendix B
11.1. Standard Function Block Parameters
440 Experion PKS Series A Fieldbus Interface Module User's Guide R400
Honeywell July 2010
blocks will perform their FSTATE action
FF Data Type
Unsigned 8
Range
1: Clear
2: Active
Usage
C/Contained
Length
1
Valid Views
VIEW_1, VIEW_3
Storage
Non-Volatile
Remarks
Read Only
FEATURES
Classification
Simple Variable
Description
Bit string that identifies the supported resource block
options.
FF Data Type
Bit String
Range
Set by manufacturer
Usage
C/Contained
Length
2
Valid Views
VIEW_4
Storage
Static
Remarks
Read Only
FEATURE_SEL
Classification
Simple Variable
Description
Bit string that identifies the selected resource block options.
FF Data Type
Bit String
Range

Table of Contents