11. Appendix B 
11.1. Standard Function Block Parameters 
430  Experion PKS Series A Fieldbus Interface Module User's Guide   R400 
 Honeywell July 2010 
Range 
1 to Manufacturer Limit 
Usage 
C/Channel 
Length 
2 
Valid Views 
VIEW_4 
Storage 
Static 
Remarks 
The initial value is 0.  
 
 
CLR_FSTATE 
 
Classification 
Simple Variable 
Description 
Serves as a switch to reset/clear the device fault state state 
after the fault condition is cleared.  
FF Data Type 
Unsigned 8 
Range 
1: Off 
2: Clear 
Usage 
C/Contained 
Length 
1 
Valid Views 
 
Storage 
Dynamic 
Remarks 
The operator can control PROGRAM or LOCAL access to 
these values. 
 
 
CONFIRM_TIME 
 
Classification 
Simple Variable 
Description 
Defines the time between retries of alert reports.  
FF Data Type 
Unsigned 32 
Range 
Positive