EasyManua.ls Logo

Honeywell Series A - Sel_3

Honeywell Series A
560 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11. Appendix B
11.1. Standard Function Block Parameters
476 Experion PKS Series A Fieldbus Interface Module User's Guide R400
Honeywell July 2010
Range
Usage
I/Cascade Input
Length
5
Valid Views
VIEW_1, VIEW_3
Storage
Non-Volatile
Remarks
Read Only
The data type consists of the value and status of floating
point parameters that are Inputs or Outputs. It uses the
following two elements.
1 Status
2 Value
SEL_3
Classification
Record
Description
Represents third input value to the selector.
FF Data Type
DS-65
Range
Usage
I/Cascade Input
Length
5
Valid Views
VIEW_1, VIEW_3
Storage
Non-Volatile
Remarks
Read Only
The data type consists of the value and status of floating
point parameters that are Inputs or Outputs. It uses the
following two elements.
1 Status
2 Value

Table of Contents

Related product manuals