6. Operation
6.3. Monitoring Fieldbus Functions Through Monitoring Tab
R400 Experion PKS Series A Fieldbus Interface Module User's Guide 253
July 2010 Honeywell
6.3 Monitoring Fieldbus Functions Through Monitoring
Tab
Inactivating/Activating a Link
Use the following procedure to inactivate/activate a fieldbus Link through the Monitoring
tab in Control Builder.
ATTENTION
Inactivating a fieldbus Link essentially shuts downs the Link and the CIOM-A
FIM, if both Links are inactivated, and interrupts the transfer of data to the
Experion system. Be sure your system can tolerate the lost of live data, while
the link is inactive.
TIP
You can initiate this same function through the corresponding Detail display
in Station.
Step Action Result
1
In Monitoring tab, click LINK icon.
Click the Toggle State button in
the toolbar.
Opens Change State dialog box.